DESCRIPTION 

 

The B4001 Conventional control and indicating equipment forms the central part of a fire detection and alarm system. The 2- wire B4001 is compatible with BHAFFCO conventional devices.

The B4001 comes standard with features that allows flexibility and expandability. Default configuration programming facilitates out-of-box installation and rapid commissioning.

The B4001 control and indicating equipment provides fire detection and alarm system designers with an economical product for life safety and property protection applications

 

 

FETURES 

• 2, 4 or 8 detection zones
• Supports up to 32 Conventional devices per alarm zone circuit
• Configurable non-latching alarm zones1
• Configurable alarm dependency (zone coincidence detection)2
• Configurable timer to delay output activation (up to 10 min)
• Capacitor end-of-line device
• 3 Access Levels
• Single-person test mode
• Day/night mode configurable
• Manual activation of alarm devices
• Auxiliary DC 24 V output, with short-circuit protection
• Programmable non-addressable alarm output circuit
• 2 unmonitored relay contacts for Fire Alarm Condition outputs
• 1 unmonitored relay contact for Fault Condition output
• 3 voltage-free inputs for remote reset, evacuation start/stop, and Day/Night mode
• Optional detection zone N/O and N/C relay outputs
• Optional remote LED detection zone displays
• Clear alarm zone LED indicators, with a single indicator for Fault, Disable and Test Condition indication
• Recessed mounting enclosure
• Supports up to 7 Repeater Panels
• Easy installation

 

 

B4001-01F

B4001-02F

B4001-03F

Power Supply

 

 

 

Operating voltage

AC (85 ~ 260) V / 50/60 Hz

Mains supply current limit

720 mA @ AC 230 V

Mains supply fuse

4 A / AC 250 V slow blow (20 mm)

Mains supply fault threshold voltage

≤ AC 60 V

Power supply

2.2 A @ DC 28.5 V

Quiescent current (Imin)

45 mA

Maximum continuous output current (Ia, max)

0.425 A

Maximum continuous output current (Ib, max)

1.3 A

Standby battery maximum capacity (2 × DC 12 V)

7.2 Ah

Maximum battery current draw

1.5 A @ maximum operating temperature

Battery fuse

6 A resettable (electronic fuse)

Battery fault threshold voltage

< DC 20 V

Battery fault threshold internal resistance

0.5 Ω

Detection Zones

 

Detection zone circuits

2

4

8

Number of connected devices per detection zone circuit

32

Detector zone quiescent current

5 mA

Detector zone alarm current

40 mA

80 mA

160 mA

Detector zone wiring characteristics (max)

40 Ω / 0.47 µF

Detection zone end-of-line capacitor

10 µF / DC 50 V

Manual call point resistor value

(470 ~ 689) Ω

Alarm Zones

 

Alarm zone outputs

2

Alarm zone current

700 mA

Alarm zone end-of-line resistor

100 kΩ

Alarm zone monitoring

Open- and short-circuit

Alarm zone voltage (max)

DC 27.5 V

Alarm zone fuse

1.1 A resettable (electronic fuse)

Ancillary Outputs

 

Number of programmable output relays

2

Ancillary fire C/O relay

2 × (1.0 A @ DC 30 V / 1 A @ AC 240 V)

Ancillary fault N/C relay

1.0 A @ DC 30 V / 1 A @ AC 240 V

Auxiliary supply

DC (12.0 ~ 28.2) V @ 200 mA

Auxiliary supply at Ib, min

DC (19.5 ~ 29.0) V @ 0 mA

Ancillary Inputs

 

Evacuation start / stop

Non-latching, voltage-free

Day / Night mode

Non-latching, voltage-free

Remote reset

Non-latching, voltage-free

Miscellaneous

 

Terminal wiring

(0.4 ~ 2.5) mm2

Operating temperature

(0 ~ +50) °C

Operating humidity

(0 ~ 95) % RH, non-condensing

Storage temperature

(-25 ~ +80) °C

Storage humidity

(0 ~ 98) % RH, non-condensing

Dimensions (h × w × d)

(402 × 337 × 99) mm

Weight (excluding batteries)

4.0 kg