			DESCRIPTION
The B4001 Conventional control and indicating equipment forms the central part of a fire detection and alarm system. The 2- wire B4001 is compatible with BHAFFCO conventional devices.
The B4001 comes standard with features that allows flexibility and expandability. Default configuration programming facilitates out-of-box installation and rapid commissioning.
The B4001 control and indicating equipment provides fire detection and alarm system designers with an economical product for life safety and property protection applications
FETURES
• 2, 4 or 8 detection zones
• Supports up to 32 Conventional devices per alarm zone circuit
• Configurable non-latching alarm zones1
• Configurable alarm dependency (zone coincidence detection)2
• Configurable timer to delay output activation (up to 10 min)
• Capacitor end-of-line device
• 3 Access Levels
• Single-person test mode
• Day/night mode configurable
• Manual activation of alarm devices
• Auxiliary DC 24 V output, with short-circuit protection
• Programmable non-addressable alarm output circuit
• 2 unmonitored relay contacts for Fire Alarm Condition outputs
• 1 unmonitored relay contact for Fault Condition output
• 3 voltage-free inputs for remote reset, evacuation start/stop, and Day/Night mode
• Optional detection zone N/O and N/C relay outputs
• Optional remote LED detection zone displays
• Clear alarm zone LED indicators, with a single indicator for Fault, Disable and Test Condition indication
• Recessed mounting enclosure
• Supports up to 7 Repeater Panels
• Easy installation
| 
 | B4001-01F | B4001-02F | B4001-03F | 
| Power Supply | 
 | 
 | 
 | 
| Operating voltage | AC (85 ~ 260) V / 50/60 Hz | ||
| Mains supply current limit | 720 mA @ AC 230 V | ||
| Mains supply fuse | 4 A / AC 250 V slow blow (20 mm) | ||
| Mains supply fault threshold voltage | ≤ AC 60 V | ||
| Power supply | 2.2 A @ DC 28.5 V | ||
| Quiescent current (Imin) | 45 mA | ||
| Maximum continuous output current (Ia, max) | 0.425 A | ||
| Maximum continuous output current (Ib, max) | 1.3 A | ||
| Standby battery maximum capacity (2 × DC 12 V) | 7.2 Ah | ||
| Maximum battery current draw | 1.5 A @ maximum operating temperature | ||
| Battery fuse | 6 A resettable (electronic fuse) | ||
| Battery fault threshold voltage | < DC 20 V | ||
| Battery fault threshold internal resistance | 0.5 Ω | ||
| Detection Zones | 
 | ||
| Detection zone circuits | 2 | 4 | 8 | 
| Number of connected devices per detection zone circuit | 32 | ||
| Detector zone quiescent current | 5 mA | ||
| Detector zone alarm current | 40 mA | 80 mA | 160 mA | 
| Detector zone wiring characteristics (max) | 40 Ω / 0.47 µF | ||
| Detection zone end-of-line capacitor | 10 µF / DC 50 V | ||
| Manual call point resistor value | (470 ~ 689) Ω | ||
| Alarm Zones | 
 | ||
| Alarm zone outputs | 2 | ||
| Alarm zone current | 700 mA | ||
| Alarm zone end-of-line resistor | 100 kΩ | ||
| Alarm zone monitoring | Open- and short-circuit | ||
| Alarm zone voltage (max) | DC 27.5 V | ||
| Alarm zone fuse | 1.1 A resettable (electronic fuse) | ||
| Ancillary Outputs | 
 | ||
| Number of programmable output relays | 2 | ||
| Ancillary fire C/O relay | 2 × (1.0 A @ DC 30 V / 1 A @ AC 240 V) | ||
| Ancillary fault N/C relay | 1.0 A @ DC 30 V / 1 A @ AC 240 V | ||
| Auxiliary supply | DC (12.0 ~ 28.2) V @ 200 mA | ||
| Auxiliary supply at Ib, min | DC (19.5 ~ 29.0) V @ 0 mA | ||
| Ancillary Inputs | 
 | ||
| Evacuation start / stop | Non-latching, voltage-free | ||
| Day / Night mode | Non-latching, voltage-free | ||
| Remote reset | Non-latching, voltage-free | ||
| Miscellaneous | 
 | ||
| Terminal wiring | (0.4 ~ 2.5) mm2 | ||
| Operating temperature | (0 ~ +50) °C | ||
| Operating humidity | (0 ~ 95) % RH, non-condensing | ||
| Storage temperature | (-25 ~ +80) °C | ||
| Storage humidity | (0 ~ 98) % RH, non-condensing | ||
| Dimensions (h × w × d) | (402 × 337 × 99) mm | ||
| Weight (excluding batteries) | 4.0 kg | ||